14 MDS iNET ENI Supplement MDS 05-4131A01, Rev. A
2.3 iNET/ENI Error Codes
Refer to Table 2-2 for error codes generated by the iNET/ENI.
Table 2-2 iNET/ENI Error Codes
Error Code Description of Error Condition
10H Target node cannot respond because of incorrect
command parameters or unsupported command.
Possible causes:
• The message’s data size is not valid
• The data format is incorrect for any of the supported
PCCC messages
• Register parameters are not formatted correctly, or
there is not enough data provided
• RS-232 configuration packet data is not the correct
size
• The Node Address is invalid or out-of-range
• The distant ENI/ENIW, controller, or device may not
be responding
• There may be a break in the connection between
the ENI devices or controllers
• BOOTP/DF1 parameter is not valid
30H
Target node responded with
Remote station host is
not there, disconnected, or shutdown
.
D0H Caused by one of the following:
• No IP address configured for the network or ENI not
configured for Node Address used
• Bad command: unsolicited message error
• Bad address: unsolicited message error
• No privilege: unsolicited message error